MPC-143 controller is created for data logging and analyzing in a real time. Using GPRS/GSM controller, sends saved data and reports to remote users.
Controller supports most of protocols and interfaces (RS232, RS485, MBUS, Optoeq, Discrete inputs), so it can be used with different brands and models of counters. Our special “TRANSPARENT” data transfer protocol enables controllers to use with practically any device.
Device supports wide range of protocols (and can be extended by our programmers, if you need some special). For data exchange over GPRS/GSM, Ethernet and/or any Serial interfaces, controller uses Modbus TCP/IP, Modbus RTU, IEC60870-5-104:2000, SNTP and other protocols.
Our clients – GAS, Heat, Watering suppliers, Industry companies in EU, Ukraine, Central Asia.
The exceptional feature of this device - a flexible hardware and software configuration, it depends on customer needs, you can choose the desired interface and functionality.
Manufacturers code:
First interface | ||
GSM/GPRS | 4 band 850/900/1800/1900 MHz | |
Second interface (galvanically isolated) | ||
RS485 | distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s | |
RS232 | distance up to 15m, speed up to 19,2Kbit/s | |
Opto | up to 2 devices | (Kamstrup) data transfer interface |
MBus | up to 8 devices | |
Third interface (galvanically isolated) | ||
RS485 | distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s | |
RS232 | distance up to 15m, speed up to 19,2Kbit/s | |
Discrete and Analog interfaces | ||
Discrete IN | 4 | sink contact |
Analogi IN | 3 | thermo-resistance (Pt100, Pt1000), voltage or current |
Protocols | ||
Modbus RTU Modbus TCP/IP IP ICMP UDP TCP DHCP PPP ARP SNTP IEC60870-5-104:2000 DynDNS FTP server FTP client DNS client | ||
General | ||
Power | 15-36 VDC | |
Galvanic isolation | >1000V | |
Capacity | <5VA | |
Internal battery | 3,7V 500 mAh | |
External battery | battery charging current up to 200mA, acid or gel 12V battery (battery is not supplied with device). With fully loaded 7Ah battery can operate about 72 hours. | |
Regulatory approvals | ||
Electromagnetic compatibility | EN 55022:2010 EN 55024:2010 EN 61000-4-2:2009 EN61000-4-3:2006 EN61000-4-3:2006/A1:2008 EN 61000-4-3:2006/A2:2010 EN 61000-4-4:2004 EN 61000-4-4:2004/A1:2010 EN 61000-4-6:2009 | |
Safety | EN 61010-1:2001 | |
Specification | ||
CPU | ARM7 | |
Memory | archive storage 1-8 MB, independant data storage without power about 5 years | |
LED indication | ||
Status of discrete input, for each port | + | |
Serial ports read/write for each port | + | |
GSM/GPRS modem status | + | |
Programing and updating | ||
Remote | GSM/GPRS | |
Locally | RS232 or RS485 | |
Physical characteristics | ||
Dimmensions | 107x128x50 mm | |
Weight | 275 g | |
Mounting type | on DIN32 rail | |
Safety class | IP20 | |
Climate conditions | ||
Operating temperature | -30..+60 °C | |
Storage temperature | -40..+60 °C | |
Humidity range | 5-95%, non-condensing | |
Other fuetures | ||
Real time clock | + | |
MBus auto setup | + | |
24 months warranty period | + |