OVERVIEW
Controller MPC-210 designed for data reading from energy carrier meters, storing to local archive and data exchange between RS232/RS485 and Ethernet.
SPECIFICATION
Serial interfaces | RS232 or RS485 |
RS485 direction control | auto |
Supported protocols | Modbus TCP/IP, Modbus RTU, DynDNS and other |
Other interfaces | mini USB |
Serial interface data transfer speed | from 300 to 38.4 kbps |
Data archive memory | from 1 to 8 MB (2MB by default) |
Insulation breakdown voltage | > 1,5 kV |
Power supplier | 50-250VAC (50-60Hz), 50-250VDC or PoE (IEEE 802.3af) |
Power consumption | 3W |
Indication | LED (Power, TX, RX, Lan, 10/100Mbps) |
Enclosure | DIN32 rail mountable, IP20 |
Dimensions | 18 mm x 85 mm x 97 mm |
Operating conditions | from - 30 oC to + 50 oC / 80 % RH, without condensate |
Storage conditions | from - 40 oC to +60 oC |
MANUFACTURERS CODE
First interface | ||
RS485 | distance up to 1,2km, max 32 transivers, speed up to 38.4 Kbits/s | |
RS232 | distance up to 15m, speed up to 38.4Kbit/s | |
Second interface | ||
Ethernet | twisted pair, 10/100 Mbps, distance up to 100m | |
Third interface | ||
USB (device) | mini USB type B, ver. 2,0 | |
Protocols | ||
Modbus RTU Modbus TCP/IP IP ICMP UDP TCP DHCP PPP ARP SNTP IEC60870-5-104:2000 DynDNS DNS client | ||
General | ||
Power | 50-250 VAC 50-60Hz, 50-250 VDC or PoE | |
Capacity | 300mA MAX | |
CPU | Cortex M3 | |
Memory | archive storage 1-8 MB, independant data storage without power about 5 years | |
LED indication | ||
Serial ports read/write for each port | + | |
Ethernet status | + | |
Programing and updating | ||
Remote | Ethernet (RJ45) | |
Locally | USB | |
Physical characteristics | ||
Dimmensions | 17x85x97 mm | |
Weight | 105 g | |
Mounting type | on DIN32 rail | |
Safety class | IP20 | |
Climate conditions | ||
Operating temperature | -25..+60 °C | |
Storage temperature | -40..+60 °C | |
Humidity range | 5-95%, non-condensing | |
Other fuetures | ||
24 months warranty period | + |
|