MPC-730 Compare

Main features:

  • Freely chosen interfaces: up to 4 interfaces.
  • Wireless M–bus. Modes S, T, R, C. OMS (Open metering system) supported.
  • Supported interfaces: RS485, RS232, Data/Req (Kamstrup), Mbus, Current loop, GSM/GPRS, WCDMA/HSPA and LAN.
  • Supported protocols: Modbus RTU, Modbus TCP/IP, IP, ICMP, UDP, TCP, DHCP, PPP, ARP, SNTP, IEC60870-5-104:200 and transparent, DynDNS, DNS(client), FTP(server&client).
  • Routing: GSM - Ethernet rounting
  • Special: transparent non-standart protocol data transfer
  • Memory expansion: up to 8GB using micros SD card
  • Power: 9-36 VDC (10VA)
  • Power for external devices: 3,7; 5; 6; 8 or 10 VDC (20mA)

Description
Specification
Usage
Downloads


OVERVIEW

Controller supports most of protocols and interfaces (RS232, RS485, Data/Req, MBus, Current loop), so it can be used with different brands and models of counters. Embedded RF module suitable for automated meter reading applications (AMR) where enhanced RF range is required, Wireless M-Bus modes S,T,R,C. Our special “TRANSPARENT” data transfer protocol enables controllers to use with practically any device.Device supports wide range of protocols (and can be extended by our programmers, if you need some special). For data exchange over GPRS/GSM, WCDMA/HSPA, Ethernet and/or any Serial interfaces, controller uses Modbus TCP/IP, Modbus RTU, IEC60870-5-104:2000, SNTP and other protocols.Our clients – GAS, Heat, Watering suppliers, Industry companies in EU, Ukraine, Central Asia.

DEFAULT FEATURES

  • Reading data from energy carrier meters;
  • Reading data from Wireless M-bus meters;
  • "TRANSPARENT” remote data reading from counters (special manufacturers protocols);
  • Independent data log (up to 8MB) with real time stamp;
  • Remote configuration and upgrading possibilities over GPRS/GSM, WCDMA/HSPA and Ethernet;
  • Wide range of interfaces: GSM/GPRS, WCDMA/HSPA, Ethernet, RS232, RS485, Data/Req, MBus Current Loop, USB;
  • Galvanically isolated interfaces and power supply;

BENEFIT TO THE CLIENT

  • Economy, because controller does a lot of mechanic work, so your professionals can do more important work;
  • Increase efficiency, because the data are sent to a central computer continuously. If connection is lost, data will be safe kept in controllers memory, until connection will be reestablished;
  • Increases security, because the relevant information is rapidly shorten response time;
  • Versatile, because this controller can retrieve data from different manufacturers and even different types of meters;
  • Simplicity, because of intuitive control and optimally assembled LED’s it is easy to monitor and maintain equipment;
  • A good partner, because we not only help you customize and will make equipment, but also flexibly adapt controller, if your demands will change.

CUSTOMIZING DEVICE

The exceptional feature of this device - a flexible hardware and software configuration, it depends on customer needs, you can choose the desired interface and functionality.

Manufacturers code:

 

For routing

in complex projects of data collection and processing

First interface
RS232distance up to 15m, speed up to 19,2Kbit/s, GSM modem support
GSM/GPRS4 band 850/900/1800/1900 MHz
Second interface (galvanically isolated)
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Opto(Kamstrup) data transfer interface
MBusup to 8 devices
2 wire active Current Loop25-27V, 14-20mA, up to 6km, speed up to 19,2Kbit/s
Third interface (galvanically isolated)
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Opto(Kamstrup) data transfer interface
MBusup to 8 devices
2 wire active Current Loop25-27V, 14-20mA, up to 6km, speed up to 19,2Kbit/s
Fourth interface
RS485distance up to 1,2km, max 32 transivers, speed up to 19.2 Kbits/s
RS232distance up to 15m, speed up to 19,2Kbit/s
Fifth interface
Wireless M–busT, S, R, C modes (433 MHz or 868 MHz, depending on market)
Protocols
Modbus RTU
Modbus TCP/IP
IP
ICMP
UDP
TCP
DHCP
PPP
ARP
SNTP
IEC60870-5-104:2000
DynDNS
FTP server
FTP client
DNS client
General
Power9-36 VDC
Galvanic isolation>1000V
Capacity300mA max
Power for external devices3,7/5/6/8/10 VDC (20mA)
Regulatory approvals
Specification
CPUARM7
SD card supportmicro SD card up to 8GB
Memoryarchive storage 1-8 MB, independant data storage without power about 5 years
LED indication
Power+
Serial ports read/write for each port+
GSM/GPRS modem status+
Ethernet status+
Programing and updating
RemoteGSM/GPRS, Ethernet (RJ45)
LocallyUSB, RS232, RS485
Physical characteristics
Dimmensions147x128x50 mm
Weight400 g
Mounting typeon DIN35 rail
Safety classIP20
Climate conditions
Operating temperature-25..+60 °C
Storage temperature-40..+60 °C
Humidity range5-95%, non-condensing
Other fuetures
Real time clock+
MBus auto setup+
24 months warranty period+