OVERVIEW
Tank level alarm LS-2 intended for level alarming of electrically conductive fluid (petrol-water, oil-water). When set level is reached, controller is switching relay (NO and NC relay contacts can be used).
LS2 operation principle is based on resistance measuring of electrically conductive fluid. Sensor contains two Stainless Steel electrodes, when electrodes flood - measuring circuit resistance is changing and LS-2 switching to alarm mode.
Set of Level alarm LS-2 contains 1 or 2 sensors (by default one), distribution box, wire for sensor and control unit.
SPECIFICATION
Sensing sensitivity adjustment | yes (3,0 kΩ, 30,0 kΩ, 300 kΩ, 3MΩ) |
MAX distance betwean controller and sensor | ≤50 m |
Amount of channels | 2 |
Sensor spark protection | yes |
Electricity insulation breakdown voltage | >1,5 kV |
Reaction in to electrically conductive fluid | NO or NC (relay contacts) |
MAX relay load | switching contacts 6A, 220V |
Power | 220V~, 50-60Hz |
Consumption | 3W |
Signaling | LED signalization |
Dimmensions | 130mm x 94mm x 57mm |
Weight | 0,3 kg |
Operation mode | 24/7 |
Controller operating mode | from -30 ºC to + 50 ºC, humidity up to 95 % (non- condensing) |
Sensors operating mode | from + 1 ºC to + 45 ºC |
Complies to electromagnetic directives | EN 61326-1:2013 EN 55011:2009 EN 55011:2009/A1:2010 EN 61000-4-2:2009 EN 61000-4-3:2006 EN 61000-4-3:2006/A1:2008 EN 61000-4-3:2006/A2:2010 EN 61000-4-4:2012 EN 61000-4-5:2006 EN 61000-4-6:2009 EN 61000-4-8:2010 EN 61000-4-11:2004 |
Complies to safety directives | EN 61010-1:2010 |
|